CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
4-8
CAUTION
Failure to replace the cylinder at the end of
cylinder life may result in humidi er damage.
NOTE
Decrease the humidity setpoint below ambi-
ent humidity to allow the cylinder to cool down
before removing the cylinder.
1. If your unit is equipped with an E² controller, turn
the A/C unit off by pressing (and holding) the
Enter key.
2. Turn off the water supply to the humidi er.
3. Turn the main power disconnect switch on the
electric box to the Off position. Remove the cover
from the electric box.
4. Fashion a jumper wire and install it across the
terminals on the Air Flow Switch
(F40).
5. Using a pair of vise grips, turn the
shaft of the main power switch to
the On position to provide power
for the humidi er drain solenoid.
6. Drain the cylinder by pushing
the “On-Off-Drain” switch to the
“Drain” position.
7. After the cylinder has drained, push the “On-Off-
Drain” switch to the “Off” position.
CAUTION
Do not leave the “On-Off-Drain” switch in the
“Drain” position for longer than 10 minutes or
the drain solenoid could burn out.
8. Remove the jumper wire from the Air Flow switch
and turn the main power disconnect switch Off to
disconnect power from the humidi er.
9. The power wires to the cylinder are attached by
cylinder plugs to the electrode pins on top of the
cylinder. Pull these plugs vertically off the pins.
CAUTION
The cylinder and steam hose may be hot and
burns may result.
10. Loosen the steam hose clamp(s) and pull the
steam hose off vertically.
11. Using a athead screwdriver, press the tab on
the cable tie to release it. Lift the cylinder straight
up to disengage it from the humidi er.
12. Place the new cylinder on the side mounting slots
within the unit, ensuring the cylinder mounting
stubs are seated properly.
13. Replace the cylinder plugs on the pins, ensur-
ing the white sensor plug goes on the single pin,
which is offset from the others.
14. Ensure the plugs are secured on the pins. If
the plugs are loose, they may be temporarily
squeezed together, however, the plugs must
be replaced since a loose plug could generate
enough heat to melt and destroy the plug.
15. Replace the steam hose and tighten the
clamp(s).
16. Push the “On-Off-Drain” switch to the “On” posi-
tion.
17. Replace the cover on the electric box and turn
the main power disconnect switch to the On
position.
18. Turn on the water supply to the humidi er.
19. If your unit is equipped with an E² controller, turn
the A/C unit On by pressing the Enter key.
20. Readjust the humidity to the desired setpoint.
If the humidi er is to be shut down for an extended
period, always drain the cylinder rst. Follow the
above steps (1 through 8 ensuring the “On-Off-Drain”
switch is in the Off position. Failure to do this will
drastically shorten the cylinder life.
4.3.4.5 Filter Replacement
The lters are located either internal or external to
the cabinet depending on the con guration of the
unit. Regardless of location, the lter is accessed
through an access panel, which is labeled “FILTER
ACCESS”. Remove access panel and old lter.
Ensuring directional air ow arrows on lter are
correct, insert new lter and replace the access
panel.