CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-6
2.5.2 Ducted Systems (See Figure 3)
There are three basic configurations of airflow patterns: 90º/Right Angle, Straight-Thru and In/Out Same-Face.
When determining ducting requirements, always consult your local and state codes. The duct system should be
designed to allow the air to move with as little resistance as possible. Several factors determine ducting material
and size. These factors are predetermined, refer to your ducting system schematic.
The connection of ducting to the unit is typically accomplished with a one-inch duct flange. Supply air outlet and
return air inlet ducts will require a field provided duct flange (refer to the installation drawing provided with the unit).
The connection of ductwork to the unit may be made with either pop rivets or self-tapping screws.
2.6 Piping Connections
2.6.1 Refrigerant
2.6.1.1 Self-Contained Systems
No refrigeration connections are required for self-
contained air, water or glycol-cooled systems (Models
OHS-012/040-AS, OHS-012/120-C and OHS-012/120-
W/G-( )).
2.6.1.2 Split Systems
Split air-cooled systems will require field refrigeration
piping. All split systems are shipped with a dry
nitrogen charge of 50 psig.
2.6.1.2.1 Remote Air Cooled Condensers
(AR Models)
Systems utilizing air cooled condensers must not have
a refrigerant line pressure drop over 14 psig across the
condenser and the interconnecting piping to the
condenser sections.
If the condenser is installed above the evaporator, the
discharge line should include a P-trap at the evapora-
tor.
Figure 3- Ducted System Typical Air Patterns
NOTE
Ensure proper condenser selection to maintain
reasonable subcooling temperatures.
If the condenser is installed below the evaporator, an
inverted trap the height of the evaporator coil is required
on the liquid line to help prevent oil and liquid from
flooding back to the compressor during off cycles.
Refer to the Recommended Discharge Line and
Recommended Liquid Line sizing tables on page 2-7.
All refrigeration piping should be installed with high
temperature brazed joints. Use standard refrigeration
practices for piping supports, leak testing, dehydration
and charging of the refrigeration circuits. The refrigera-
tion piping should be isolated from the building by the
use of vibration isolating supports. To prevent tube
damage when sealing openings in walls and to reduce
vibration transmission, use a soft flexible material to
pack around the tubes.