CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
4-3
SYMPTOM PROBABLE CAUSE RECOMMENDATION
Evaporator Coil Ices (Cont.) 2. Check for and clear any
obstructions across or in the (supply)
discharge airstream.
3. Check correct rotation of
evaporator blower.
b. Temperature setting Increase temperature
too low (68°F min.). setpoint.
c. Discharge air short cycling back Check discharge grille orientation.
to return.
d. Low refrigerant charge. Find leak, repair and recharge
system.
Blower Fails to Start a. Power failure. Check main voltage power source
input cable.
b. Control transformer circuit breaker Check for short circuit or ground
tripped. fault; if none, reset circuit breaker.
c. Defective contactor. Repair or replace.
d. Condensate switch open. 1. Ensure unit is level.
2. Check that condensate pan is
draining properly. Clear obstructions.
e. Thermal overload tripped. Reset overload and check amperage
of motor. Compare to setting on
overload and adjust to FLA. All direct-
drive motors are internally protected
and do not require overload.
Control is Erratic Wiring - improperly connected or broken. Check wiring against schematic
diagram.
Condenser Pressure a. Non-condensable gas or air in Recover system and recharge. Install
too High the system. new drier/strainer.
b. Condenser air intake is blocked. Remove debris and clean condenser.
c. Overcharge of refrigerant. Reclaim excess refrigerant from
system.
d. Low water flow to water-cooled Reset-determine cause and fix.
condenser.
e. Condenser fan not operating. Check pressure/temperature
operating switches and motor.
Replace as needed.
f. Water/glycol temperature too high. Check flow and operation of
drycooler.
g. Condenser pressure regulating Adjust to obtain correct pressure.
valve setting too high.
h. Flow of water/glycol too low. 1. Check glycol solution level and
concentration.