CeilAiR OHS Series Installation, Operation & Maintenance Manual
ir Technology Systems, Inc.
2-16
2.7.3.3 Remote Water Detector
Spot Type:
A remote spot type water detector requires three
conductors to be wired to the control terminal board
within the unit electrical box. The wire insulation must
be rated at 600V. The water detector provides pig-tail
leads for splice type wire connections with twist on
connectors (wire caps). Refer to the supplied electrical
diagram for proper wire terminations.
Strip/Cable Type:
A remote strip/cable type water detector is provided
with a two conductor cable harness with a quick
connect fitting on the end. The harness mates to the
fitting on the water detector and connects it to the
control board inside the electric box. Refer to the
supplied electrical diagram for proper wire termina-
tions.
2.7.4 Air-Cooled Split Systems
The following system interconnecting field wiring
sections detail the number of conductors required for a
typical system. Additional control conductors may be
required depending on the options purchased with the
equipment. Refer to the supplied electrical diagram to
determine the total number of interconnecting conduc-
tors required for your system. It is important to note
that the control transformer(s) supplied with the
equipment have been sized and selected based upon
the expected loads for each system.
CAUTION
Do not connect any additional loads to the sys-
tem control transformers. Connecting additional
loads to the factory supplied control
transformer(s) may result in overloading of the
transformer.
NOTE
All wiring must be provided in accordance with
local and national electrical code requirements
for Class 2 circuits.
2.7.4.1 Remote Condenser (See Figure 9)
Systems equipped with a remote condenser require
field wiring between the evaporator system and the
remote condenser. Refer to the supplied electrical
schematic and the wiring diagram supplied with the
condenser (typically located in the condenser electric
box). The installer must provide main power wiring to
the main power distribution block located within the
remote condenser control box. A separate equipment
ground lug is provided within the electrical box for
termination of the earth ground wire.
The installer must also wire two control conductors
from the terminal board within the evaporator unit to
the control terminal board within the remote condenser
control box. Refer to the supplied electrical diagram for
proper wire terminations.
2.7.4.2 Remote Condensing Unit
(See Figure 10 and 11)
Systems equipped with a remote condensing unit
require field wiring between the evaporator system and
the remote condenser unit. The number of conductors
required between the two systems varies based upon
the number of options provided. A single stage cooling
system typically requires three conductors. Refer to
the supplied electrical diagram(s) to determine the
exact amount of field wires and proper wire termina-
tions required for your specific unit.
2.7.5 Water/Glycol Systems (See Figure 12)
The following system interconnecting field wiring
sections detail the number of conductors required for a
typical system. Additional control conductors may be
required depending on the options purchased with the
equipment. Refer to the supplied electrical diagram to
determine the total number of interconnecting conduc-
tors required for your system. It is important to note
that the control transformer(s) supplied with the
equipment have been sized and selected based upon
the expected loads for each system.
CAUTION
Do not connect any additional loads to the sys-
tem control transformers. Connecting additional
loads to the factory supplied control
transformer(s) may result in overloading of the
transformer.
NOTE
All wiring must be provided in accordance with
local and national electrical code requirements
for Class 2 circuits.
Systems equipped with a glycol-cooled system/pump
package require field wiring between the glycol unit and
pump package. The installer must wire two control
conductors from the terminal board within the glycol unit
to the pump package electrical box. Refer to the supplied
electrical schematic for proper wire terminations.